Backflow assembly test · Station Diner
ApprovedFiled Aug 25, 2024 by Hayden Okafor, Northstar Backflow Testing · filed from phone
Report
- Date of service
- Aug 25, 2024
- Assembly type
- DC
- Serial number
- A452902
- Size
- 2
- Test gauge serial
- G-1672
- Gauge calibration date
- Mar 2, 2024
- Check valve 1
- 7.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 131-28-01201
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.