Backflow assembly test · Station Diner

Approved

Filed Oct 1, 2025 by Emerson Benton, Summit Backflow Testing · filed from phone

Report

Date of service
Oct 1, 2025
Assembly type
DC
Serial number
A452902
Size
2
Test gauge serial
G-5790
Gauge calibration date
Mar 29, 2025
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 131-28-01201
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.