Sebastian County, ARCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Self Storage

Approved

Filed Oct 25, 2025 by Logan Okafor, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Oct 25, 2025
Assembly type
RP
Serial number
A749539
Size
1 1/2
Test gauge serial
G-2356
Gauge calibration date
Jan 19, 2025
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 131-92-01178
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

1986 Spring Branch Trl
Owner: Whitcomb Holdings LLC
Parcel 131-92-01178