Backflow assembly test · Golden Self Storage

Approved

Filed Oct 23, 2025 by Hayden Okafor, Northstar Backflow Testing · filed from phone

Report

Date of service
Oct 23, 2025
Assembly type
DC
Serial number
W261680
Size
1 1/2
Test gauge serial
G-6866
Gauge calibration date
May 15, 2025
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 131-47-01117
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.