Backflow assembly test · Blue Heron Animal Hospital
ApprovedFiled Jun 29, 2023 by Parker Ashby, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Jun 29, 2023
- Assembly type
- RP
- Serial number
- B715997
- Size
- 4
- Test gauge serial
- G-7542
- Gauge calibration date
- Apr 3, 2023
- Check valve 1
- 5.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 131-69-01172
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
6527 Orchard Dr
Owner: Danner Holdings LLC
Parcel 131-69-01172