Backflow assembly test · 3499 Sycamore Ct

Approved

Filed Sep 4, 2025 by Hayden Okafor, Northstar Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Sep 4, 2025
Assembly type
DC
Serial number
B230501
Size
3/4
Test gauge serial
G-3938
Gauge calibration date
Apr 22, 2025
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 131-88-01332
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.