Backflow assembly test · 411 Orchard Dr
Needs reviewFiled Nov 22, 2026 by Reese Fairley, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Nov 22, 2026
- Assembly type
- RP
- Serial number
- W379026
- Size
- 3/4
- Test gauge serial
- G-6039
- Gauge calibration date
- Oct 15, 2026
- Check valve 1
- 3.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 143-57-01077
- Readings in range, no flags
- Result: passing. Next due date resets when approved.