Washington County, ARCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Golden Market

Approved

Filed Mar 11, 2026 by Reese Fairley, Clearwater Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Mar 11, 2026
Assembly type
DC
Serial number
B957236
Size
1
Test gauge serial
G-9088
Gauge calibration date
Jan 19, 2026
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 143-24-01010
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

5181 Hickory Way
Owner: Nguyen Holdings LLC
Parcel 143-24-01010