Backflow assembly test · Corner Apartments

Approved

Filed Oct 7, 2025 by Taylor Pruitt, Summit Backflow Testing · filed from phone

Report

Date of service
Oct 7, 2025
Assembly type
RP
Serial number
B961319
Size
1
Test gauge serial
G-9470
Gauge calibration date
Mar 19, 2025
Check valve 1
4.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 143-55-01030
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2286 Ridgeview Rd
Owner: Okafor Holdings LLC
Parcel 143-55-01030