Backflow assembly test · 8063 Stone Gate Rd
ApprovedFiled May 12, 2024 by Reese Fairley, Clearwater Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- May 12, 2024
- Assembly type
- RP
- Serial number
- Z870736
- Size
- 3/4
- Test gauge serial
- G-4500
- Gauge calibration date
- Oct 28, 2023
- Check valve 1
- 8.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 143-66-01230
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
8063 Stone Gate Rd
Owner: Quinn Brandt
Parcel 143-66-01230