Backflow assembly test · 8759 Spring Branch Ct
ApprovedFiled Dec 6, 2025 by Alex Benton, Heritage Plumbing & Backflow · filed from phone
Report
- Date of service
- Dec 6, 2025
- Assembly type
- RP
- Serial number
- A991623
- Size
- 1
- Test gauge serial
- G-5325
- Gauge calibration date
- Feb 21, 2025
- Check valve 1
- 3.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-84-01296
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.