Backflow assembly test · Crossroads Bakery
Needs reviewFiled Nov 15, 2026 by Parker Kessler, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Nov 15, 2026
- Assembly type
- RP
- Serial number
- K639454
- Size
- 4
- Test gauge serial
- G-2533
- Gauge calibration date
- Feb 11, 2026
- Check valve 1
- 5.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-20-01211
- Readings in range, no flags
- Result: passing. Next due date resets when approved.