Backflow assembly test · 1353 Turkey Hill Way
ApprovedFiled Sep 24, 2023 by Quinn Nguyen, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Sep 24, 2023
- Assembly type
- PVB
- Serial number
- K411544
- Size
- 1
- Test gauge serial
- G-4370
- Gauge calibration date
- May 4, 2023
- Check valve 1
- 8.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-55-01318
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.