Backflow assembly test · Crossroads Grill
ApprovedFiled Jul 17, 2026 by Avery Ellery, Keystone Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Jul 17, 2026
- Assembly type
- RP
- Serial number
- A862151
- Size
- 4
- Test gauge serial
- G-1056
- Gauge calibration date
- Sep 25, 2025
- Check valve 1
- 8.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-46-01283
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.