Backflow assembly test · 707 Orchard Ct
ApprovedFiled Dec 2, 2025 by Rowan Okafor, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Dec 2, 2025
- Assembly type
- RP
- Serial number
- Z161731
- Size
- 3/4
- Test gauge serial
- G-8687
- Gauge calibration date
- Sep 4, 2025
- Check valve 1
- 6.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 4.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-56-01257
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.