Alameda County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 205 Laurel Ct

Approved

Filed Nov 28, 2023 by Quinn Nguyen, Keystone Backflow Testing · filed from phone

Report

Date of service
Nov 28, 2023
Assembly type
RP
Serial number
B731661
Size
3/4
Test gauge serial
G-2900
Gauge calibration date
Sep 4, 2023
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-69-01170
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

205 Laurel Ct
Owner: Hayden Calloway
Parcel 001-69-01170