← Backflow review queue
Backflow assembly test · 3624 Hickory Way
ApprovedFiled Aug 1, 2025 by Avery Ellery, Keystone Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Aug 1, 2025
- Assembly type
- DC
- Serial number
- W851604
- Size
- 1
- Test gauge serial
- G-6695
- Gauge calibration date
- Apr 26, 2025
- Check valve 1
- 8.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-72-01143
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3624 Hickory Way
Owner: Drew Nguyen
Parcel 001-72-01143