← Backflow review queue
Backflow assembly test · 6425 Stone Gate Ct
ApprovedFiled Sep 23, 2026 by Logan Kessler, Valley Backflow Testing · filed from phone
Report
- Date of service
- Sep 23, 2026
- Assembly type
- RP
- Serial number
- A571566
- Size
- 3/4
- Test gauge serial
- G-9219
- Gauge calibration date
- Jun 20, 2026
- Check valve 1
- 4.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 1.3 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-94-01005
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
6425 Stone Gate Ct
Owner: Emerson Fairley
Parcel 009-94-01005