Backflow assembly test · 3134 Spring Branch Way
ApprovedFiled Aug 22, 2025 by Sam Ellery, Summit Backflow Testing · filed from phone
Report
- Date of service
- Aug 22, 2025
- Assembly type
- RP
- Serial number
- W595790
- Size
- 1
- Test gauge serial
- G-6832
- Gauge calibration date
- Nov 12, 2024
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-65-01066
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3134 Spring Branch Way
Owner: Emerson Whitcomb
Parcel 009-65-01066