Calaveras County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Golden Dental

Approved

Filed Sep 1, 2024 by Avery Pruitt, Valley Backflow Testing · filed from phone

Report

Date of service
Sep 1, 2024
Assembly type
RP
Serial number
Z665906
Size
2
Test gauge serial
G-3336
Gauge calibration date
Dec 14, 2023
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-89-01133
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5759 Spring Branch Way
Owner: Ashby Holdings LLC
Parcel 009-89-01133