Backflow assembly test · 6116 Hickory Ln
ApprovedFiled Dec 20, 2025 by Logan Kessler, Valley Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Dec 20, 2025
- Assembly type
- PVB
- Serial number
- W812792
- Size
- 1
- Test gauge serial
- G-7513
- Gauge calibration date
- Nov 25, 2024
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-85-01073
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
6116 Hickory Ln
Owner: Jordan Ramirez
Parcel 009-85-01073