Backflow assembly test · 7918 Fox Run Rd
ApprovedFiled Jun 2, 2024 by Emerson Marsh, Summit Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Jun 2, 2024
- Assembly type
- DC
- Serial number
- K640008
- Size
- 1
- Test gauge serial
- G-1725
- Gauge calibration date
- Jan 28, 2023
- Check valve 1
- 0.2 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-98-01056
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7918 Fox Run Rd
Owner: Cameron Benton
Parcel 009-98-01056