← Backflow review queue
Backflow assembly test · Blue Heron Car Wash
ApprovedFiled Aug 24, 2025 by Avery Pruitt, Valley Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Aug 24, 2025
- Assembly type
- RP
- Serial number
- Z838551
- Size
- 2
- Test gauge serial
- G-1221
- Gauge calibration date
- Jul 1, 2025
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-50-01169
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
1520 Spring Branch Ct
Owner: Calloway Holdings LLC
Parcel 009-50-01169