← Backflow review queue
Backflow assembly test · 4234 Turkey Hill Trl
Needs reviewFiled Nov 24, 2026 by Logan Kessler, Valley Backflow Testing · filed from phone
Report
- Date of service
- Nov 24, 2026
- Assembly type
- RP
- Serial number
- Z420702
- Size
- 1
- Test gauge serial
- G-5713
- Gauge calibration date
- Aug 21, 2026
- Check valve 1
- 4.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-28-01180
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
4234 Turkey Hill Trl
Owner: Sam Fairley
Parcel 009-28-01180