← Backflow review queue
Backflow assembly test · 4086 Orchard Dr
ApprovedFiled Oct 14, 2025 by Avery Pruitt, Valley Backflow Testing · filed from phone
Report
- Date of service
- Oct 14, 2025
- Assembly type
- RP
- Serial number
- K251394
- Size
- 1
- Test gauge serial
- G-2704
- Gauge calibration date
- Jul 25, 2025
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-10-01323
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
4086 Orchard Dr
Owner: Drew Ashby
Parcel 009-10-01323