Calaveras County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Station Pizza

Approved

Filed Mar 29, 2025 by Rowan Marsh, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Mar 29, 2025
Assembly type
RP
Serial number
W518736
Size
2
Test gauge serial
G-5294
Gauge calibration date
Jan 2, 2024
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
1.8 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-65-01327
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2051 Hickory Way
Owner: Ramirez Holdings LLC
Parcel 009-65-01327