Calaveras County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Station Pizza

Approved

Filed May 6, 2026 by Blake Ellery, Valley Backflow Testing · filed from phone

Report

Date of service
May 6, 2026
Assembly type
RP
Serial number
W518736
Size
2
Test gauge serial
G-7602
Gauge calibration date
Sep 20, 2025
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-65-01327
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

2051 Hickory Way
Owner: Ramirez Holdings LLC
Parcel 009-65-01327