Backflow assembly test · 4154 Pine Knoll Rd
ApprovedFiled Jun 3, 2023 by Jamie Whitcomb, Northstar Backflow Testing · filed from phone
Report
- Date of service
- Jun 3, 2023
- Assembly type
- RP
- Serial number
- K728840
- Size
- 3/4
- Test gauge serial
- G-8282
- Gauge calibration date
- Oct 17, 2022
- Check valve 1
- 7.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-75-01189
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.