← Backflow review queue
Backflow assembly test · 4154 Pine Knoll Rd
ApprovedFiled May 30, 2024 by Blake Marsh, Patriot Backflow Testing · filed from phone
Report
- Date of service
- May 30, 2024
- Assembly type
- RP
- Serial number
- K728840
- Size
- 3/4
- Test gauge serial
- G-5841
- Gauge calibration date
- Oct 25, 2023
- Check valve 1
- 3.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 1.8 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-75-01189
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
4154 Pine Knoll Rd
Owner: Reese Wexler
Parcel 013-75-01189