← Backflow review queue
Backflow assembly test · Main Street Dental
ApprovedFiled Sep 9, 2025 by Morgan Ashby, Valley Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Sep 9, 2025
- Assembly type
- RP
- Serial number
- A694544
- Size
- 4
- Test gauge serial
- G-4622
- Gauge calibration date
- Feb 11, 2025
- Check valve 1
- 5.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 4.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-62-01073
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
904 Meadow Lark Way
Owner: Whitcomb Holdings LLC
Parcel 013-62-01073