Contra Costa County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 5236 Hickory Trl

Approved

Filed Jul 13, 2026 by Parker Ashby, Northstar Backflow Testing · filed from phone

Report

Date of service
Jul 13, 2026
Assembly type
RP
Serial number
A197888
Size
3/4
Test gauge serial
G-5505
Gauge calibration date
Dec 20, 2025
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-94-01171
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5236 Hickory Trl
Owner: Blake Ashby
Parcel 013-94-01171