Backflow assembly test · 805 Old Church Way
ApprovedFiled Sep 11, 2026 by Jamie Whitcomb, Northstar Backflow Testing · filed from phone
Report
- Date of service
- Sep 11, 2026
- Assembly type
- PVB
- Serial number
- A748674
- Size
- 1
- Test gauge serial
- G-6079
- Gauge calibration date
- May 21, 2026
- Check valve 1
- 4.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-32-01307
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
805 Old Church Way
Owner: Morgan Benton
Parcel 013-32-01307