Backflow assembly test · 3699 Orchard Ct
ApprovedFiled Jul 28, 2026 by Parker Stroud, Valley Backflow Testing · filed from phone
Report
- Date of service
- Jul 28, 2026
- Assembly type
- RP
- Serial number
- W774257
- Size
- 3/4
- Test gauge serial
- G-8239
- Gauge calibration date
- Apr 22, 2026
- Check valve 1
- 7.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 017-56-01277
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3699 Orchard Ct
Owner: Drew Benton
Parcel 017-56-01277