Backflow assembly test · 4190 Spring Branch Dr
ApprovedFiled Nov 6, 2025 by Avery Wexler, Valley Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Nov 6, 2025
- Assembly type
- RP
- Serial number
- A198722
- Size
- 3/4
- Test gauge serial
- G-9605
- Gauge calibration date
- Apr 8, 2025
- Check valve 1
- 5.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 017-96-01241
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
4190 Spring Branch Dr
Owner: Blake Wexler
Parcel 017-96-01241