Backflow assembly test · 9001 Spring Branch Ln

Approved

Filed Jul 25, 2025 by Avery Ashby, Summit Backflow Testing · filed from phone

Report

Date of service
Jul 25, 2025
Assembly type
RP
Serial number
A294046
Size
1
Test gauge serial
G-4039
Gauge calibration date
Nov 18, 2024
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 017-58-01051
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.