← Backflow review queue
Backflow assembly test · 4731 Spring Branch Rd
ApprovedFiled Nov 6, 2024 by Avery Ashby, Summit Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Nov 6, 2024
- Assembly type
- DC
- Serial number
- Z413630
- Size
- 3/4
- Test gauge serial
- G-6723
- Gauge calibration date
- Jan 14, 2024
- Check valve 1
- 3.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 017-87-01048
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4731 Spring Branch Rd
Owner: Sam Ellery
Parcel 017-87-01048