Backflow assembly test · 9012 Turkey Hill Rd

Approved

Filed Aug 24, 2026 by Riley Brandt, Valley Plumbing & Backflow · filed from phone

Report

Date of service
Aug 24, 2026
Assembly type
DC
Serial number
B277159
Size
3/4
Test gauge serial
G-1106
Gauge calibration date
Mar 3, 2026
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 017-39-01248
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.