Backflow assembly test · 7725 Turkey Hill Dr
ApprovedFiled Aug 8, 2023 by Emerson Hollins, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Aug 8, 2023
- Assembly type
- RP
- Serial number
- B589222
- Size
- 3/4
- Test gauge serial
- G-9429
- Gauge calibration date
- May 31, 2023
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-66-01054
- Readings in range, no flags
- Result: passing. Next due date resets when approved.