← Backflow review queue
Backflow assembly test · 4160 Stone Gate Ln
ApprovedFiled Oct 4, 2024 by Blake Pruitt, Keystone Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Oct 4, 2024
- Assembly type
- RP
- Serial number
- W500932
- Size
- 1
- Test gauge serial
- G-5849
- Gauge calibration date
- Jun 1, 2023
- Check valve 1
- 6.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 1.4 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-37-01103
- RP relief valve must open at 2.0 psid or more.
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4160 Stone Gate Ln
Owner: Quinn Pruitt
Parcel 025-37-01103