Backflow assembly test · 1553 Quarry Dr
ApprovedFiled Sep 24, 2023 by Blake Pruitt, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Sep 24, 2023
- Assembly type
- RP
- Serial number
- Z263639
- Size
- 1
- Test gauge serial
- G-2402
- Gauge calibration date
- Feb 19, 2023
- Check valve 1
- 3.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-25-01022
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.