← Backflow review queue
Backflow assembly test · 1435 Sycamore Trl
Needs reviewFiled Nov 26, 2026 by Avery Vance, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Nov 26, 2026
- Assembly type
- RP
- Serial number
- A719670
- Size
- 3/4
- Test gauge serial
- G-3471
- Gauge calibration date
- Sep 12, 2026
- Check valve 1
- 0.2 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 4 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-94-01207
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Property
1435 Sycamore Trl
Owner: Sam Kessler
Parcel 025-94-01207