Los Angeles County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 4879 Cedar Hollow Way

Approved

Filed Jul 16, 2024 by Parker Whitcomb, Ridge Backflow Testing · filed from phone

Report

Date of service
Jul 16, 2024
Assembly type
RP
Serial number
A104021
Size
3/4
Test gauge serial
G-6619
Gauge calibration date
Jan 23, 2024
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 037-90-01129
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4879 Cedar Hollow Way
Owner: Hayden Pruitt
Parcel 037-90-01129