Los Angeles County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Two Rivers Dental

Approved

Filed Dec 29, 2025 by Parker Whitcomb, Ridge Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Dec 29, 2025
Assembly type
DC
Serial number
Z145177
Size
4
Test gauge serial
G-9979
Gauge calibration date
Sep 19, 2025
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 037-99-01256
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

9870 Orchard Dr
Owner: Ashby Holdings LLC
Parcel 037-99-01256