Backflow assembly test · Hilltop Medical Offices
ApprovedFiled Jan 14, 2025 by Parker Whitcomb, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Jan 14, 2025
- Assembly type
- RP
- Serial number
- W383564
- Size
- 4
- Test gauge serial
- G-3419
- Gauge calibration date
- Sep 26, 2024
- Check valve 1
- 7.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 037-48-01094
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.