Los Angeles County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2230 Hickory Trl

Approved

Filed Aug 30, 2026 by Parker Vance, Valley Backflow Testing · filed from phone

Report

Date of service
Aug 30, 2026
Assembly type
DC
Serial number
Z778610
Size
3/4
Test gauge serial
G-5940
Gauge calibration date
Feb 9, 2026
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 037-17-01150
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2230 Hickory Trl
Owner: Shawn Pruitt
Parcel 037-17-01150