Backflow assembly test · Hilltop Self Storage
ApprovedFiled Dec 1, 2025 by Parker Whitcomb, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Dec 1, 2025
- Assembly type
- RP
- Serial number
- A925810
- Size
- 1 1/2
- Test gauge serial
- G-1231
- Gauge calibration date
- Feb 16, 2025
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 037-89-01073
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.