← Backflow review queue
Backflow assembly test · 1687 Spring Branch Ln
ApprovedFiled Nov 26, 2025 by Parker Vance, Valley Backflow Testing · filed from phone
Report
- Date of service
- Nov 26, 2025
- Assembly type
- RP
- Serial number
- Z285823
- Size
- 3/4
- Test gauge serial
- G-9479
- Gauge calibration date
- Feb 18, 2025
- Check valve 1
- 6.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 037-19-01313
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1687 Spring Branch Ln
Owner: Emerson Okafor
Parcel 037-19-01313