← Backflow review queue
Backflow assembly test · Corner Grill
ApprovedFiled May 11, 2026 by Parker Vance, Valley Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- May 11, 2026
- Assembly type
- RP
- Serial number
- A918332
- Size
- 2
- Test gauge serial
- G-7928
- Gauge calibration date
- Sep 12, 2025
- Check valve 1
- 3.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 4.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 037-88-01143
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1111 Quarry Way
Owner: Marsh Holdings LLC
Parcel 037-88-01143