Backflow assembly test · 6733 Orchard Way
Needs reviewFiled Nov 20, 2026 by Avery Wexler, Northstar Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Nov 20, 2026
- Assembly type
- RP
- Serial number
- Z607862
- Size
- 3/4
- Test gauge serial
- G-9657
- Gauge calibration date
- Sep 11, 2026
- Check valve 1
- 7.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 041-88-01174
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
6733 Orchard Way
Owner: Riley Nguyen
Parcel 041-88-01174