Marin County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 3429 Mill Creek Ct

Approved

Filed Aug 13, 2024 by Parker Harlow, Valley Backflow Testing · filed from phone

Report

Date of service
Aug 13, 2024
Assembly type
DC
Serial number
K559971
Size
1
Test gauge serial
G-4078
Gauge calibration date
Jan 31, 2024
Check valve 1
0.2 psid
Check valve 1 closed tight
No
Check valve 2
3.3 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 041-69-01022
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

3429 Mill Creek Ct
Owner: Shawn Danner
Parcel 041-69-01022